Phoenix Contact Power Supplies

Phoenix Contact / Power supplies

Four tiers, three TRIO generations, and a naming quirk where one family is rated in amps and another in watts.

Phoenix Contact DIN rail power supplies sit in most New Zealand control panels. They fail, they get replaced, and the replacement has to match the load and the panel space.

Watch the rating unit

This catches people because the families do not use the same convention.

Family Rated in Example
QUINT Amps QUINT-PS/1AC/24DC/10 is 10 A
TRIO Amps TRIO-PS/1AC/24DC/5 is 5 A
UNO Watts UNO-PS/1AC/24DC/240W is 240 W

A UNO rated 240W is a 10 A supply at 24 V. If you are comparing across families, convert before you compare, because 240W and 10 sit in the same position in the designation and mean the same thing.

The four tiers

Family Positioning
QUINT Highest specification. Diagnostics, preventive function monitoring, high power reserves
TRIO Standard functionality, optimised for machine building
STEP Basic, compact
UNO Compact, cost-focused

Phoenix describes the TRIO range as perfected for machine building, with an extremely robust electrical and mechanical design for challenging ambient conditions, and a space-saving format across single and three-phase modules.

Do not substitute down a tier without checking. A QUINT in a panel may have been chosen for its power reserve or its diagnostic contact, and a UNO of the same output will not do those things.

The generation is in the name

TRIO has three generations and they are different parts.

Name Generation Connection
TRIO-PS Original Screw
TRIO-PS-2G Second Push-in
TRIO3-PS Third Push-in

QUINT follows the same idea: QUINT-PS and QUINT4-PS are different generations.

So a TRIO-PS/1AC/24DC/5 and a TRIO-PS-2G/1AC/24DC/5 have the same output and are not the same part. Check the terminals as well, because the newer generations moved to push-in.

How the designation decodes

Take TRIO-PS/1AC/24DC/5, order number 2866310.

Part Meaning
TRIO-PS Family and generation
1AC Single-phase AC input
24DC 24 V DC output
5 5 A output

Input codes

Code Input
1AC Single-phase AC
100-240AC Single-phase, wide range
3AC, 3X400-500AC Three-phase AC
24DC 24 V DC input, a DC to DC converter

A 24DC input unit is a converter, not a mains power supply. QUINT-PS-24DC/24DC/10 takes 24 V in and gives isolated 24 V out. Fitting one where a mains supply was expected gives you nothing.

Confirmed TRIO order numbers

Order number Type Output Notes
2866310 TRIO-PS/1AC/24DC/5 24 V DC, 5 A, 120 W Input 100 to 240 V AC, 50/60 Hz
2903148 TRIO-PS-2G/1AC/24DC/5 24 V DC, 5 A Push-in connection
1159039 TRIO3-PS/1AC/24DC/20 24 V DC, 20 A Push-in, adjustable 24 to 28 V DC

The TRIO3 output is adjustable from 24 to 28 V DC. Useful on a long DC run where volt drop matters, since you can lift the supply end to land 24 V at the load.

Confirmed QUINT order numbers

Order number Type
2866750 QUINT-PS/1AC/24DC/5
2866763 QUINT-PS/1AC/24DC/10
2938581 QUINT-PS-100-240AC/24DC/5
2938879 QUINT-PS-100-240AC/24DC/40
2904484 QUINT-PS-100-240AC/24DC/40/SO1
2866255 QUINT-PS-100-240AC/48DC/5
2938976 QUINT-PS-100-240AC/48DC/20
2938617 QUINT-PS-3X400-500AC/24DC/10
2320092 QUINT-PS-24DC/24DC/10
2320102 QUINT-PS/24DC/24DC/20
2904600 QUINT4-PS/1AC/24DC/5
2904601 QUINT4-PS-1AC/24DC/10
2320393 QUINT-BUFFER/24DC/24DC/40

Also in the range: QUINT-PS/1AC/24DC/20, a 20 A single-phase unit.

UNO, and a superseded part worth knowing

Order number Type Status
2904372 UNO-PS/1AC/24DC/240W Superseded. Phoenix directs new systems to 1096432

Phoenix Contact states plainly that 1096432 should be used in new systems.

That matters two ways. If you are building new, specify the current part. If you are replacing a failed 2904372 in an existing panel, you may still want the original for a like-for-like fit, and that is where we can help.

Buffer modules and UPS are not power supplies

Easy to mistake in a parts list.

Type What it does
QUINT-BUFFER Holds the 24 V rail up through a brief supply dip. Sits alongside the supply
QUINT-UPS Uninterruptible supply with a battery, for longer outages
QUINT-DIODE, QUINT-ORING Redundancy modules for combining two supplies

A QUINT-BUFFER/24DC/24DC/40 has 24 V in and 24 V out and is not a mains power supply. If your panel has one, it works with the supply rather than instead of it. Replacing a failed supply with a buffer gives you a panel that will not power up.

Redundancy modules matter where two supplies feed one rail. Wiring two supplies in parallel without one is not the same thing.

What to check when replacing a supply

Output current or wattage. Note which unit the family uses.

Output voltage. 24 V DC is usual but 48 V and 12 V exist in the range.

Input phase. Single or three phase, and whether it is actually a DC to DC converter.

Connection type. Screw on older generations, push-in on newer. If the panel is wired for one, the other means reterminating.

Width. A higher-rated supply is usually wider. On a full rail that decides whether it fits.

Signal contacts. Many units have a DC OK relay or signal output wired into the PLC. A replacement without it leaves an input dead and a fault that looks like something else.

Send us the order number and we will match all of it. If the label is unreadable, tell us the output voltage and current and what else is wired to it.

Sizing a new supply

Two things worth saying because they cause callbacks.

Inrush matters more than steady state. A panel full of contactor coils, relay modules and PLC power supplies draws far more at switch-on than in normal running. QUINT units in particular are specified with power reserves for exactly this.

Leave headroom. Panels get added to. A supply sized exactly to today's load is the reason someone is replacing it in three years.

What we can supply

Current production. QUINT, QUINT4, TRIO, TRIO-2G, TRIO3, STEP and UNO across the range, plus buffer modules, UPS, redundancy modules and batteries. Quoted with a delivered lead time.

Superseded and discontinued. Earlier QUINT and TRIO generations, and parts like the 2904372 where the current replacement does not fit the existing panel. Surplus and tested used.

That second category is where we are most useful. A like-for-like replacement in an existing panel avoids reterminating and rewiring the signal contacts.

Related

Phoenix Contact overview. Terminal blocks.

For power supplies from other brands see Omron S8 range and the Siemens SITOP range on our Siemens page.

Send us your order numbers

The seven-digit number is definitive. Tell us whether the existing unit has a signal contact wired in, because that is easy to miss and awkward to discover later. Quotes in NZD including GST.

Request a quote


Industech is an independent supplier of new, surplus and used industrial automation equipment. We are not an authorised distributor of, approved by, sanctioned by, or affiliated with Phoenix Contact GmbH & Co. KG. Phoenix Contact, QUINT, TRIO POWER, STEP POWER and UNO POWER are trademarks of Phoenix Contact. All trademarks, brand names and order numbers are the property of their respective owners and are used here for identification purposes only.

New

With a great range of the top brands, make us part of your next project.

Asset realization

Ask us about our asset realization program to turn your unused spare parts into cash instead of letting them collect dust on the shelf.

Legacy equipment

With our professional expertise, we can help you source and acquire those elusive legacy parts at competitive prices.

What Makes Us Different?

We make it our business to understand your business

We take the time to understand your needs and goals for your plant or project, with reliability and longevity as our top priorities.

Ethical Pricing

At Industech, we take pride in our ethical pricing structure, ensuring you receive the best value we can offer.

We supply new, surplus and cost-effective alternatives from major industrial brands including:

  • IFM
  • Siemens
  • Lenze
  • B&R Automation
  • ABB
  • Rockwell Automation (Allen Bradley)
  • Schneider Electric
  • Berger Lahr
  • PILZ
  • Sick
  • Emerson Electric
  • Festo
  • Beckhoff
  • Omron Corporation
  • General Electric (GE)
  • Banner
  • Keyence
  • HBM and so much more.

Maximizing Efficiency with Industry-Leading Automation and Monitoring Spares for Your Business

We take pride in providing professional, reliable, and cost-effective alternatives to new automation and control parts from all major brands.