Danfoss VLT HVAC Drive FC-102 and AQUA Drive FC-202, New Zealand
Danfoss / VLT HVAC Drive FC-102 and AQUA Drive FC-202
An FC-102 and an FC-202 of the same rating are close to the same hardware. What you are paying for is the application software: deragging and pipe fill on the AQUA, fire mode and building protocols on the HVAC. A physically identical drive of the wrong type will run the motor and not do the job it was bought for.
These are the two Danfoss ranges we are asked for most on New Zealand infrastructure. FC-202 on water and wastewater, FC-102 on building services and process ventilation.
Which one do you have
| FC-102 HVAC Drive | FC-202 AQUA Drive | |
|---|---|---|
| Built for | Fans, pumps and compressors in buildings | Water and wastewater pumping |
| Signature functions | Fire mode, energy optimisation, scheduling, resonance skip | Deragging, pipe fill, dry run detection, flow compensation |
| Protocols | Building management protocols alongside the industrial ones | Industrial fieldbus and telemetry |
| Predecessor | VLT 6000 | VLT 6000 |
Both replaced the VLT 6000, which is why a single legacy range maps to two current ones. Which of the two a station should get depends on whether it is a building or a pump.
The type code tells you which you have. Send it rather than the kW rating.
The AQUA functions, and why they were specified
These are the reason an FC-202 was bought instead of a general purpose drive. If the station relies on one of them, a substitute has to have it.
Deragging
The wastewater function that saves the most call-outs. The drive detects a rising load or a torque signature that suggests a clogged impeller, then runs a sequence of forward and reverse pulses to shake the rag off.
So a pump that used to clear itself and now blocks weekly may simply have had its drive replaced with something that does not derag. That presents as a pump problem and it is a drive specification problem.
Worth asking about on any wastewater station where blockage call-outs have increased.
Pipe fill mode
Fills an empty pipe slowly to avoid water hammer. On a long rising main, filling at full speed can shock the pipework and the valves.
If a station has a documented history of burst joints or valve damage and someone specified pipe fill, that is what it is doing.
Dry run and no-flow detection
Detects that the pump is running without water and stops it before the seal is destroyed. It works from the relationship between speed and power rather than needing a flow switch.
That is a protection function. A replacement drive without it leaves the pump unprotected, and the failure it prevents is expensive.
Sleep mode and flow compensation
| Function | What it does |
|---|---|
| Sleep mode | Stops the pump at low demand rather than running it at minimum speed |
| Flow compensation | Reduces the pressure setpoint as flow falls, because friction loss falls too |
| End of curve detection | Detects the pump running past its curve, usually a burst or an open valve |
| Check valve ramp | Controls the stop so the check valve does not slam |
Sleep mode and flow compensation are energy functions and they were often the justification for the drive. Losing them does not stop the station, it just quietly costs money.
The cascade controller
Important when there is more than one pump, and the most disruptive thing to get wrong.
One drive acts as the cascade master and stages the other pumps in and out to meet demand, alternating them to equalise run hours.
| Consequence |
|---|
| The master holds the cascade configuration. The followers do not |
| Replacing the master without its parameter set stops the staging, and one pump ends up doing all the work |
| Run hour alternation resets, so wear stops being shared |
So on a multi-pump station, find out which drive is the master before you replace anything. Tell us and we will flag it on the quote.
The HVAC functions
Fire mode is a life safety function
The most important thing on the FC-102 side.
Fire mode makes the drive keep running the fan through conditions that would normally trip it, so a smoke extraction or stairwell pressurisation fan continues to operate during a fire.
| Point | Detail |
|---|---|
| It is configured, not automatic | A default drive does not have it set up |
| It usually has a dedicated input | Triggered by the fire panel |
| It overrides normal protection | Deliberately. The fan runs until it cannot |
So a replacement drive commissioned from defaults does not provide fire mode, and the fan will trip on the fault that fire mode was there to ignore.
If the drive is on a smoke extraction or pressurisation duty, say so. That is a compliance item and the parameter set matters more than the hardware. Whether a configuration meets the building's fire engineering belongs with whoever holds that documentation.
Building management protocols
The FC-102 talks to building systems as well as industrial ones. That is a large part of why it exists as a separate product.
Support is split between what is built in and what needs an option card, and it varies by generation and by protocol. Send the type code and tell us what the BMS speaks, and we will confirm what the drive needs.
If the drive sits on a building network rather than a PLC, that is the question to settle before ordering.
Resonance skip and broken belt detection
| Function | Why it was set up |
|---|---|
| Bypass frequency, resonance skip | The fan or duct resonates at a particular speed. The drive refuses to run there |
| Broken belt detection | Low load at speed means the belt has gone. Stops a fan running to nothing |
| Automatic Energy Optimisation | Trims magnetising current on a part loaded motor |
| Real time clock and scheduling | Timed start, stop and setback |
Resonance skip is worth knowing about because the symptom of losing it is noise and vibration, not a fault. A replacement drive at defaults will happily sit at the frequency the original was told to avoid, and the plant room gets loud.
And the real time clock needs a battery. If scheduling has stopped working or the clock resets, that is a consumable rather than a drive fault.
Enclosure rating matters more on these ranges
Because of where they live.
| Code | Rating | Typical location |
|---|---|---|
| E20 | IP20 | Inside a switchboard |
| E55 | IP55 | Wall mounted in a plant room or pump station |
| E66 | IP66 | Washdown, outdoor kiosk, reservoir site |
An IP20 drive is not a replacement for an IP55 or IP66 one unless it is going inside an enclosure that provides the protection instead. On a reservoir kiosk or a wastewater site, the drive's own rating is usually the protection.
And conformal coating is a separate question from IP rating. A sealed enclosure keeps water out and does not stop hydrogen sulphide attacking the board. On wastewater, ask for the coated version.
The option slots are shared with the AutomationDrive
FC-102 and FC-202 use the same MCA fieldbus and MCB I/O option families as the FC-301 and FC-302. The slots and the cards are covered in detail on our AutomationDrive page.
Two that come up often on these ranges:
| Option | Why here |
|---|---|
| MCB 114 sensor input | Temperature sensors for motor or process monitoring |
| MCB 105 relay card | Extra relay outputs for valves, alarms and pump staging |
| MCB 107 24 V backup | Keeps the drive on the telemetry through a supply dip. Common on remote stations |
The 24 V backup is the one worth checking on a remote site. If a pump station stops reporting to SCADA every time the supply flickers, and another station does not, that option is the difference.
Where the value actually sits
Worth being direct about, because it changes what you should buy.
On these two ranges the parameter set is worth more than the drive. A commissioned FC-202 on a wastewater station carries the deragging thresholds, the pipe fill ramp, the dry run limits, the cascade staging and the protection settings for that specific station and its hydraulics.
| Situation | Outcome |
|---|---|
| Identical drive plus LCP 102 parameter copy | Swap and run. Minutes |
| Identical drive, no backup | Recommissioning against whatever documentation exists |
| Different type or generation | Recommissioning, and the functions have to be reconfigured from scratch |
So the cheapest thing any water authority or facilities team can do is take an LCP 102 round the site and copy the parameter set off every running drive. One panel, an afternoon, and every future failure becomes a swap.
We supply LCP 102 panels separately for exactly this.
Before ordering a replacement
| Symptom | Check first |
|---|---|
| Pump blocking more often than it used to | Whether deragging is configured, or was lost in a swap |
| One pump doing all the work on a multi-pump station | The cascade master and its alternation |
| Plant room noisy at one particular speed | Resonance skip, lost at defaults |
| Smoke extraction fan trips instead of running | Fire mode configuration |
| Scheduling stopped or clock resetting | The real time clock battery |
| Drive drops off telemetry on every supply dip | MCB 107 24 V backup |
| Board corroded on a wastewater site | Whether the original was conformal coated |
| Overtemperature in a sealed kiosk | Cooling fan, filter and the kiosk itself |
What to send us
The full type code. It carries the range, power, voltage, IP rating, filter class, brake and coating.
Whether it is FC-102 or FC-202. Same hardware family, different application software.
What the drive is doing. Wastewater pump, rising main, smoke extraction, chilled water. That tells us which functions matter.
Whether it is a cascade master.
Whether the duty is fire related.
Whether the site is wet, corrosive or outdoors, for IP rating and coating.
What is in the option slots.
Whether you have a parameter backup.
What we can supply
Drives. FC-102 and FC-202 across the power ratings and voltage classes, in IP20, IP55 and IP66, coated and uncoated, braked and unbraked.
The related ranges. FC-101 HVAC Basic and FC-103 Refrigeration, which share the platform.
Option cards. MCA fieldbus, MCB I/O, relay, sensor and 24 V backup options.
Panels. LCP 101 and LCP 102, and blanking plates.
Parts. Cooling fans, filters, real time clock batteries and braking resistors.
Where a build is no longer available new we supply surplus and tested used, which keeps a station on its original parameter set.
We buy FC-102 and FC-202
Both ranges hold value, and IP55 and IP66 units more so because they are what water sites actually need. Coated units are worth more again.
If a station is being upgraded, keep the LCP with the drive and the option cards in their slots, and tell us if a drive came out of wastewater so we can describe the coating correctly. See Sell To Us.
Common questions
Can you get a part that is not listed on your site?
Usually. The site shows what we hold, not what we can source.
Can I use an FC-302 instead of an FC-202?
It will run the pump. It does not have deragging, pipe fill, dry run detection or the cascade controller. On a wastewater station that matters.
Can I use an FC-202 instead of an FC-102?
For a straightforward fan or pump, usually yes. Not if the duty needs fire mode or a building protocol.
My pump keeps blocking since the drive was replaced.
Check whether deragging is configured. That is the most common version of this question.
Is IP66 worth it?
On an outdoor kiosk or a washdown area, yes. It is also not a substitute for conformal coating on wastewater.
Do you supply used equipment?
Yes, where new is not available. Used drives are powered up and tested before they ship.
What is the lead time?
Ex stock items ship the next working day within New Zealand. We give you a firm lead time with the quote.
Do you quote in NZD?
Yes, in NZD including GST for New Zealand customers.
Related
Danfoss overview, FC-301 and FC-302 AutomationDrive and VLT 2800, 5000 and 6000, which is what these two replaced.
For pump and fan drives from other brands see ABB ACS580, Siemens SINAMICS G120, Schneider Altivar and Mitsubishi FR-F800.
Send us your type codes
Tell us what the drive is doing as well as what it is. On these two ranges the application decides the product. Quotes in NZD including GST.
Industech is an independent supplier of new, surplus and used industrial automation equipment. We are not an authorised distributor of, approved by, sanctioned by, or affiliated with Danfoss. Danfoss, VLT, HVAC Drive and AQUA Drive are trademarks of Danfoss A/S. BACnet is a trademark of ASHRAE. All trademarks, brand names and type codes are the property of their respective owners and are used here for identification purposes only.
Forestry
Manufacturing
Mining
Agricultural
FMCG
Petrochemical
Pharmaceutical
BMS
New
With a great range of the top brands, make us part of your next project.
Asset realization
Ask us about our asset realization program to turn your unused spare parts into cash instead of letting them collect dust on the shelf.
Legacy equipment
With our professional expertise, we can help you source and acquire those elusive legacy parts at competitive prices.
What Makes Us Different?
We make it our business to understand your business
We take the time to understand your needs and goals for your plant or project, with reliability and longevity as our top priorities.
Ethical Pricing
At Industech, we take pride in our ethical pricing structure, ensuring you receive the best value we can offer.
We supply new, surplus and cost-effective alternatives from major industrial brands including: